北京嘉泰国际大厦空调机房噪声治理 李昆王笑鹏顾深 中冶建筑研究总院有限公司, 北京 100088 摘要 北京嘉泰国际大厦因在建筑设计和施工阶段未对空调机房采用合理的噪声控制措施, 导致竣工后噪声达不到用 户的要求, 无法使用。只能花更大的精力和代价进行改造和治理。以此为实例, 分析其噪声振动超标的原因, 并简述 治理方案及最终效果。最后提出大厦机房建造和振动噪声控制方面的建议。 关键词 空调机房; 振动噪声; 隔振; 隔声 DOI 10. 7617/j. issn. 1000 -8942. 2013. 05. 018 NOISE CONTROL OF AIR- CONDITIONING ROOM IN BEIJING JIATAI INTERNATIONAL BUILDING Li KunWang XiaopengGu Shen Central Research Institute of Building and Construction Co. , Ltd,MCC Group,Beijing 100088,China AbstractThe reasonable measures of noise control were not taken at the stages of building design and construction of the air- conditioning room in Beijing Jiatai International Building,so it couldnt meet the noise requirements of users and couldn’ t be used. Only more energy and costs should be spent to re. It was analyzed the causes of making noise and vibration exceed the standard,and the treating scheme of the project and the final result were described. Finally,it was proposed the suggestions on the machine room construction and the vibration and noise control. Keywordsair- conditioning room;vibration noise;vibration isolation;sound insulation 随着社会经济发展, 大量高档、 时尚、 现代化的宾馆 饭店、 写字楼、 高级公寓、 商场、 展馆等大型综合建筑物层 出不穷, 其中尤以高层建筑发展最快; 其内部配套设施 的配置不断完善、 档次不断提高、 规模不断扩大。随之 而来的是各种机组设备对建筑物内、 外部环境的噪声振 动影响也越来越突出。如何紧跟建筑业技术、 设备、 规 格更新发展的步伐, 配合设计院和开发商完善各类现代 建筑中各种系统、 各类设备内外部噪声振动控制配套设 计或后期改造工程, 是近年来建筑工程和环保专业的热 门话题, 更是考验各从业单位技术实力的试金石。工程 实践表明, 现代建筑物中噪声振动控制措施的同步设 计、 制造、 安装, 是一项复杂、 综合的系统工程, 要求我们 以严谨的科学态度在每一个环节上都尽可能做到合理、 匹配、 到位, 否则必然面临被动改造的局面。 1治理前情况 嘉泰国际大厦 B 座空调冷冻机房位于地下一 层, 机房内装有约克离心式制冷机组 2 台、 冷却、 冷冻 循环泵各 3 台。目前设备下已加减振器, 管道连接及 固定采用单球橡胶挠性接管和弹簧减振吊架。设备 振动传递给结构问题得到一定程度的缓解。但隔振 处理存在遗漏和不合理地方, 减振器和台架的选择和 设计是否经过完整的计算需要打问号。且因机房位 于地下一层, 太靠近楼面办公区域, 因此楼面办公区 域对噪声振动影响比较敏感。设备运行时产生的振 动噪声沿管路和建筑结构传递, 形成明显的固体噪声 传导辐射。对上层楼内的声环境产生严重影响, 针对 现场勘测的情况拟定切实可行的噪声振动治理方案, 可让上层楼内有一个安静舒适的工作和休闲环境。 对机房噪声振动进行了测量, 冷水机组的工作负 荷为 59 时, 噪声测量结果为 冷水机组旁 1 m 90 dB; 冷冻水泵旁 1 m 87 dB; 空调机房正上方办公 室内最大噪声 59 dB。振动加速度测量结果 冷水机 组旁地面 0. 21 m/s2, 冷冻水泵旁地面 0. 08 m/s2 , 空 调机房正上方办公室地面 0. 06 m/s2, 一层大厅商品 87 环境工程 2013 年 10 月第 31 卷第 5 期 柜旁地面 0. 04 m/s2。 2声源、 振源分析 对嘉泰国际 B 座楼面房间的影响主要来自地下 机房冷冻机组及各类循环系统的水泵、 管路及其他设 备运行时产生的噪声振动, 冷冻机组及水泵的管路系 统对声环境影响最大, 主要是管路系统产生的结构噪 声传导。经过分析得出 结构振动传声是主要的, 但 空气传声也不可忽视。 3治理标准和降噪量要求 根据 GB 223372008社会生活环境噪声排放 标准 中对结构传播固定设备室内噪声排放限值的 规定, 噪声敏感建筑物所处1 类声环境下的 B 类房间 指主要在昼间使用, 需要保证思考和精神集中、 正 常讲话不被干扰的房间, 包括学校教师、 会议室、 办公 室、 住宅中卧室以外的其他房间等 昼间噪声不高于 45 dB, 夜间噪声不高于35 dB。由于一层办公室并不 在深夜使用, 按 45 dB 控制。测量扣除背景噪声影 响。算得降噪量不小于 14 dB。 4方案设计 根据现场情况与上述要求和问题相应采用隔振 与隔声兼顾的做法。分别对隔声和隔振做设计。隔 振方案 1 将冷冻机组拆开, 在基座下安装高效能阻 尼弹簧隔振器、 减振垫 见图 1 。2 将机组进排口单 球软接头更换成双球橡胶软接头 见图 1 。3 将循 环水泵拆开, 剔除水泥基础后找平层, 安装隔振钢架、 减振器、 减振垫 见图 2 。4 将循水泵进排口单球软 接头更换成双球橡胶软接头 见图 2 。5 拆除管路 刚性托、 吊架, 将主要部位的管路支撑架、 吊架改装成 弹性支撑架及弹性吊架 见图 3 。6 剔凿机房管路 系统的穿墙部位, 做弹性隔振包扎。 图 1冷水机组隔振措施示意 Fig.1The sketch of vibration isolation measures for cooling water unit 隔声方案 1 对机房内部顶部及四周局部墙体 做隔声处理, 隔声层由外到内结构为 0. 8 mm 厚镀锌 穿孔钢板 50 mm 离心玻璃棉 2. 5 mm 厚钢板 涂 阻尼漆50 mm 厚离心玻璃棉 见图4 。2 考虑到 图 2水泵组隔振措施示意 Fig. 2The sketch of vibration isolation measures for water pump 图 3管道吊架示意 Fig. 3The sketch of pipeline hanger 尽量不增加声桥, 不使用吊杆来悬吊顶部隔声结构。 采用在地面起热轧槽钢支柱来支撑顶部钢构架。现 场的墙面和顶面有电线盒、 仪表箱、 电器柜等, 需要根 据现场情况而定, 这些地方避开建立柱和支撑槽钢。 3 原机房隔声门向外开。为增加隔声量, 将门做成 双层, 增加向内开的门。机房内两扇门都做处理, 另 外监控室的门也换成带观察窗的隔声门。 图 4隔声层结构示意 Fig. 4The sketch of sound insulation layer structure 下转第 90 页 97 环境工程 2013 年 10 月第 31 卷第 5 期 [7]Tay J H, Jiang H L, Tay S T L. High rate biodegradation of phenol byaerobicallygrownmicrobialgranules [J].Journalof Environmental Engineering, 2004, 130 12 1415- 1423. [8]Liu Yong Qiang, Kong Yunhua, Tay Joo Hwa,et al. Enhancement of start- up of pilot- scale granular SBR fed with real wastewater[ J] . Separation and Purication Technology, 2011, 82 190- 196. [9]Kim J,Chen M,Kishida N,et al. Integrated real- time control strategy for nitrogen removal in swine wastewater using sequencing batch reactors[ J] . Water Res, 2004, 38 3340- 3348. [ 10]Liu Y,Wang Z W,Qin L, et al. Selection pressure driven aerobic granulation in a sequencing batch reactor[J] .Appl Microbiol Biotechnol, 2005, 67 26- 32. [ 11]SchmidtJ E,Ahring B K.Granular sludge ation in upflow anaerobic sludge blanket UASB reactors [J].Biotechnol Bioeng, 1996, 49 3 229- 246. [ 12]Rose R K. The role of calcium in oral streptococcal aggregationand the implicationsforbiofilmationandrentation [J] . BiochimBiophysActa, 2000, 1475 1 76-82. [ 13]Lei Qin,Yu Liu,Tay J H. Effect of settling time on aerobic granulationinsequencingbatchreactor [J] .Biochemical Engineering Journal, 2004, 21 47- 52. [ 14]郭建华,彭永臻,黄惠珺, 等. 好氧曝气时间实时控制实现短 程硝化[ J]. 清华大学学报. 自然科学版, 2009, 49 12 1997- 2000. [ 15]Adav S S,Lee D J,Lai J Y. Functional consortium from aerobic granules under high organic loading rates [J].Bioresource Technol, 2009, 100 3465- 3470. [ 16]吴蕾,彭永臻,王淑莹, 等. 短程硝化颗粒污泥 SBR 的快速启 动与维持[J] . 化工学报, 2010, 61 11 2931- 2937. [ 17]Rittmann BE, McCartyPL. Environmentalbiotechnology principles and applications[M] . New YorkMcGraw- Hill, 2001. [ 18]Guo Jianhua, Yang Qing, PengYongzhen,et al. Biological nitrogen removal with real time control using step feed SBR technology[J]. Enzyme Microb Tech, 2007, 40 6 1564- 1569. [ 19]Blackburne R,Yuan Z,Keller J.Demonst ration of nitrogen removal via nitrite in a sequencing batch reactor treating domestic wastewater[J] . Water Res, 2008, 42 8/9 2166- 2176. [ 20]杨庆,彭永臻,王淑莹,等. SBR 法低温短程硝化实现与稳定 的中试研究[ J] . 化工学报, 2007, 58 11 2901- 2905. 作者通信处刘国洋100124北京市朝阳区平乐园 100 号北京工 业大学建筑工程学院 E- maillgy0117 emails. bjut. edu. cn. 2012 -11 -14 櫅櫅櫅櫅櫅櫅櫅櫅櫅櫅櫅櫅櫅櫅櫅櫅櫅櫅櫅櫅櫅櫅櫅櫅櫅櫅櫅櫅櫅櫅櫅櫅櫅櫅櫅櫅櫅櫅櫅櫅櫅櫅櫅櫅櫅櫅櫅 收稿 上接第 79 页 5竣工验收情况 2011 年 7 月 4 日, 双方人员在嘉泰国际大厦 B 座 地下一层空调机房内和地上一层大厅 敏感点 进行了 噪声测试。冷水机组及水泵稳定运行工况为负荷 71, 噪声测量结果如下 冷水机组旁1 m 82 dB; 冷冻 水泵旁 1 m 79. 7 dB; 空调机房正上方办公室内 42 dB。因此可计算得到各个位置的降噪量。最主要 敏感点空调机房正上方办公室内降噪量为17 dB。 6结语及建议 因此空调机房噪声振动治理效果明显, 满足标准 规定的噪声限值要求。治理工程圆满达标, 顺利 验收。 对于新建带有空调机房的建筑, 建筑设计师往往 考虑不到噪声振动问题, 建议建筑设计师将空调机房 布置在地下二层, 总之远离地面敏感区域。如想确保 建筑建成后不发生空调机房运行带来的噪声振动问 题, 需在机房施工和设备安装阶段找专业人员做减振 降噪设计, 从而从源头解决此类问题。 参考文献 [1]周新祥. 噪声控制技术及其新进展[M]. 北京 冶金工业出版 社, 2007. [2]岳秀萍. 建筑设备的减振与消声[J] . 环境科学, 1997, 15 4 41- 43. [3]孙光苏, 孙天镭, 胡孝华, 等. 特大型冷却塔及冷水机组房噪声 治理[ J]. 环境工程, 1998, 16 2 51- 53. [4]张兴容. 隔声技术在民用工程中的应用[J] . 环境工程, 2002, 20 3 44- 45. [5]李亚峰, 刘仁勇. 室内给水排水系统的噪声与控制[J] . 环境工 程, 1999, 17 2 39- 41. 作者通信处李昆100088北京海淀区西土城路 33 号中冶建筑 研究总院有限公司 电话 010 82227673 E- maillikun- bjtu hotmail. com 2012 -12 -07 收稿 09 环境工程 2013 年 10 月第 31 卷第 5 期